Rambler's Top100
Research-Manufacturing Enterprise METRA - World Class Weighing Equipment
Ðóññêàÿ âåðñèÿ Ðóññêèé
Home Home Catalogue Catalogue Instruments Instruments Ì0801 Digital load cell signal converter Ì0801 Digital load cell signal converter
About our company
News
Industrial solutions
Catalogue
Truck scales
Car scales
Crane scales
Heavy-weight scales
Floor scales
Pallet scales
Monorail scales
Conveyor scales
Hopper scales
Flow meters
Batchers
Instruments
Weight-measuring instrument for static scales
Batching weight-measuring instrument
Conveyor weight-measuring instrument
Ì0801 Digital load cell signal converter
Load cell signal simulator
Backup panel
Interface connector
Remote control unit
Control cabinet for discrete batcher
Control cabinet for continuous batcher
Microsim 0601-BM Weight-measuring instrument
Ì0803
Load cells
Software
Accessories
Additional inquiry of the information
Search
Print page Digital load cell signal converter Print
Digital load cell signal converter

Digital load cell signal converter

Ì0801
Digital load cell signal converter

Designation It is provided for load cell analog signal conversion in a digital signal and its transfer via RS485 interface. It is built in strain-gauge systems: electronic scales, batchers, control and engineering equipment.

Benefits

  • Direct load cell connection without additional couplings;
  • 6-wire load cell connection layout;
  • high accuracy;
  • high resolution ratio (24 orders of digital code);
  • simplicity and serviceability;
  • wide temperature range (from -30 to +40 Ñ);
  • built-in galvanic isolated digital interface RS485;
  • galvanic isolated supply;
  • strain-gauge converter program update.

Description: There are three converter models:

  • Ì0801-P – as a module on a printed circuit board, protected from mechanical failures by means of safety case.
  • Ì0801-1 – in aluminum waterproof case with two cable outputs.
  • Ì0801-4 – in aluminum waterproof case with summing cardboard and five cable inputs.

Model Ì0801-4 sums up signal of four load cells connected in parallel.

Adjustment of M0801-based weight-measuring system is carried out without analog regulating elements, using computer or external terminal. Adjustment data is saved in nonvolatile storage mounted on converter cardboard; number of recording cycles is not less than 100000.

Load cell cable and digital communication cable connection is carried out via screw clamps mounted on the cardboard.

Ì0801 provides several inquiry methods via RS485: cyclic inquiry mode during operation in the network of similar devices, permanent transmission mode and answer to the inquiry.

Basic set

  • Strain-gauge converter Ì0801-(Ï/1/4);
  • Operation manual;
  • CD with basic software, including driver MpsDrv;
  • Programmer’s manual with communication protocol description.

Standard functions

  • Analog signal conversion to the digital one;
  • Signal cleaning from high-frequency pickup;
  • Preliminary signal treatment: ranging, averaging;
  • Set parameters of signal output and treatment;
  • set parameters saving in EEPROM;
  • digital signal transfer viaRS485;
  • operation in strain-gauge converter network.

Driver MpsDrv, included in the basic set, is a tool for flexible, and at the same time simple and intuitively clear strain-gauge converter adjustment. It can be used as a data transmission tool from strain-gauge converter network to the operational system, using modern COM-technology of Windows 9X/NT environment.
Technical specification
Characteristic Value
Load cell supply voltage, V +5 V DCà
5 V AC
Load resistance in load cell supply circuit 80…1000 Îì
Number of load cells connected in parallel, Rb>=350 Ohm, not more, pcs. 4
Load cell connection layout 6-ïðîâîäíàÿ
Working range of load cell signal, mV/V -0.25 … +3.75
Cable length for load cell connection, not more, m 100 ì
Main reduced error of load cell signal conversion, per year, not more, % ±0,01
Inherent nonlinearity, not more, % of total scale ±0,002
Measurement frequency, Hz 50…400
Digital interface RS485
Serial connection speed, baud 1200; 2400; 4800; 9600; 19200; 38400; 57600
Length of RS485 cable, not more, m 1200
Operating temperature range, °Ñ îò -30 äî +40
Power supply voltage, V
Power consumption, not more, VA
+10…+24 Â
0,5
Board (case) dimensions, mm 115x65x30 (175õ105õ50)
Average error-free running time, hour 10000